I’m in an apt. and the power has been shutting off lately. It doesn’t trip any of the breakers in the breaker box inside the apt. but it does trip the master breaker on the box outside. Thought it was an oven issue but it still happens with the oven breaker off.
Visual inspection of the breaker box outside shows one of the wires looks a bit corroded. Wires to/from the rest of the units are a nice copper color. Is that a red flag?
Landlord is dragging their feet and telling us to talk to the electric company, and electric company is saying to call a licensed electrician, so I’m just trying to understand the issue so hopefully the landlord will listen to me.
What you’re describing is not an issue caused by corrosion on a wire. Corrosion won’t cause overdraw or shorting, so it wouldn’t cause your main breaker to flip.
It’s more likely that you either have a weakening breaker due to age tripping at a lower draw than it was originally rated for or you’re drawing more across the entire system than the main is rated for.
The electric co does not handle anything from the first breaker on and nothing on their end would trip your breaker(it would trip something of theirs upstream), usually so they are right that you should be talking to an electrician. That is something that your landlord should be on the hook for, barring any previous agreements.
If you want to see what your circuits are drawing, consider picking up a digital clamp meter, they will make it possible to see what each circuit, including the main are actually drawing.
Electrician here, that’s heat scoring. Happens when the terminal is loose, or the draw is nearing the upper limit of the installed wire for an extended period of time (looks like #8 TW, which is not ideal to run at 50a for more than 3 hours continuously, especially for how old it is). It could also be that the breaker is old enough to not be tripping reliably. Either way, there’s enough resistance with that scoring that I’ll just keep getting worse and continually building up heat until it melts the breaker and/or burns off. An electrician needs to swap that breaker and re-pull the wire (with #6s), that’s not a utility issue.
I assume you are talking about the middle wire?
No, the wire in the bottom terminal that’s blackened
But that’s green copper oxidation
Cause by heat scoring, and beneath the traces of green oxidation is heat blackenng. That leg specifically has been over heated over time, causing the discoloration reaction. If it was natural oxidation (like the statue of liberty, for example), then all the wires would be the same color.
Copper wire for a long time has been manufactured in such a way that it is resistant to ambient oxidation. When excessive heat is induced in the wire, that natural protection is broken down and then it is subject to turning green, but generally only where heat has damaged the wire.
Here is a basic idea of how cables are made to not oxidize when they’re just sitt ng there in normal operation.
Damn, thank you for explaining, I appreciate it.
No worries